Eaton

Eaton Moeller® series CI-K Insulated enclosure

رقم القطعة: 206897

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

Eaton Moeller® series CI-K Insulated enclosure

المواصفات

Ambient operating temperature - max70 °C
Ambient operating temperature - min-25 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
Product NameEaton Moeller® series CI-K Insulated enclosure
Catalog Number206897
Model CodeCI-K4-125-M
EAN4015082068974
Product Length/Depth125 mm
Product Height240 mm
Product Width160 mm
Product Weight1.01 kg
CertificationsDIN EN 62208 IEC 60068-2-11 UL94: VO/1.5 mm thickness UL94: HB IEC/EN 60529
Source URLhttps://www.eaton.com/gb/en-gb/skuPage.206897.html
Catalog NotesLamp indicator L‐… can be mounted in base knock-out M20/M25
Suitable forEmergency stop
FeaturesUV resistance beneath protective shield Halogen free
TypeBasic enclosure
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistanceMeets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effectsMeets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiationPlease enquire
10.2.5 LiftingNot applicable.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard's requirements.
10.3 Degree of protection of assembliesMeets the product standard's requirements.
10.4 Clearances and creepage distancesMeets the product standard's requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder's responsibility.
10.8 Connections for external conductorsIs the panel builder's responsibility.
10.9.2 Power-frequency electric strengthIs the panel builder's responsibility.
10.9.3 Impulse withstand voltageIs the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating materialMeets the product standard's requirements.
Degree of protectionIP65 NEMA Other
Enclosure material1 Ω x 10¹³ (Surface resistance to IEC 60093) Plastic
Dielectric strength30 kV/mm, according to IEC 60243-1
Surface treatmentResistant to corrosion
Mounting depth98 mm
ModelSurface mounting
Fitted with:Mounting plate Control cable entry
Temperature resistance-40 - 80 °C (gasket) -40 - 120 °C (enclosure)
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss26 W
Heat dissipation per pole, current-dependent Pvid0 W
Rated operational current for specified heat dissipation (In)0 A
Static heat dissipation, non-current-dependent Pvs0 W
Product categoryEmpty enclosures
KnockoutsMetric cable entry knockouts at the top, bottom and back plate Hard knockout version
Degree of protection (front side)IP65
Enclosure colorBlack (RAL 9005) Light gray, Cover (RAL 7035) Light gray, Operator (RAL 7035)
Mounting weight capacity - max0.9 kg
Environmental resistancePartly resistant to alcohol Chemical resistant (Push-through membrane (CI-K1/CI-K2) and sealing material) Resistant against alcohol Chemical resistant (Base, Cover) Not resistant to benzene Resistant against alkalis Partly resistant to greases Resistant against greases Resistant against salt solutions Not resistant to alkalis Partly resistant to benzene Resistant against gasoline Resistant against acids (< 10%) Partly resistant to acids (> 10%) Resistant against mineral oil Resistant against benzene Not resistant to Mineral oil
Cover materialGlass-fiber reinforced polycarbonate
Flammability characteristics960 °C/1 mm thickness (base, cover; glow wire to VDE 0471 Part 2) 650 °C/1 mm thick (push-through membrane) to VDE 0471 Part 2)
Impact resistanceIK06 (according to EN 50102)
Radiated heat dissipation with separate mounting26 W (at an ambient temperature of 20 °C)
Track resistanceCTI 175 (cover, to IEC 60112) CTI 175 (base, to IEC 60112)
Water consumption0.29 % (According to DIN EN ISO 62)