Eaton Moeller® series STN Control transformer
رقم القطعة: 221526
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.


رقم القطعة: 221526
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
Eaton Moeller® series STN Control transformer
| Product Name | Eaton Moeller® series STN Control transformer |
|---|---|
| Catalog Number | 221526 |
| Model Code | STN2,5(400/230) |
| EAN | 4015082215262 |
| Product Length/Depth | 145 mm |
| Product Height | 255 mm |
| Product Width | 230 mm |
| Product Weight | 25 kg |
| Certifications | UL5085-1 VDE 0113, VDE 0100 Part 410 IEC/EN 61558-2-2 CSA-C22.2 No. 66.2-06 UL Recognized UL report applies to both US and Canada CSA-C22.2 No. 66.1-06 UL 506 UL File No.: E167225 CE Certified by UL for use in Canada UL 5085-2 UL Category Control No.: XPTQ2, XPTQ8 VDE 0570 Part 2-2 CSA-C22.2 No. 66 IEC/EN 60204-1, ÖVE-EN 13 |
| Source URL | https://www.eaton.com/gb/en-gb/skuPage.221526.html |
| Catalog Notes | Electrical characteristics: all details for no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values relate to a temperature of 20 °C |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0 W |
| Rated operational current for specified heat dissipation (In) | 0 A |
| Static heat dissipation, non-current-dependent Pvs | 166 W |

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر

Eaton
اطلب عرض سعر