ABB

E45DU-45

رقم القطعة: 1SAX211001R1102

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

ريليه إلكتروني للحماية من التحميل الزائد E45DU-45، ثلاثي الأقطاب

المواصفات

Extended Product TypeE45DU-45
Product ID1SAX211001R1102
EAN4016779666619
Catalog DescriptionE45DU-45 Electronic Overload Relay 15 ... 45 A
Long DescriptionThe E45DU-45 is an self-supplied electronic overload relay, which means no extra external supply is needed. It offers reliable and fast protection for motors in the event of overload or phase failure. Easy to use like a thermal overload relay and compatible with standard motor applications, the electronic overload relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the contactors. Single mounting kits are available as accessory.
Display NameE45DU-45
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Data Sheet, Technical Information1SBC100173C0201
Instructions and Manuals2CDC107013M5502
Product Net Width45 mm
Product Net Depth / Length85.1 mm
Product Net Height97 mm
Product Net Weight0.35 kg
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles3P
StandardsIEC/EN 60947-1
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC
Rated Frequency (f)Auxiliary Circuit 50 Hz
Rated Insulation Voltage (U<sub>i</sub>)690 V
Rated Impulse Withstand Voltage (U<sub>imp</sub>)Auxiliary Circuit 6 kV
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 2.5 ... 10 mm²
Wire Stripping LengthAuxiliary Circuit 9 mm
Degree of ProtectionIP20
Recommended Screw DriverAuxiliary Circuit Pozidriv 2
Tightening TorqueAuxiliary Circuit 0.8 ... 1.2 N·m
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 14-6 AWG
Tightening Torque UL/CSAAuxiliary Circuit 7 in·lb
Ambient Air TemperatureOperation -25 ... +70 °C
Maximum Operating Altitude Permissible2000 m
Pollution Degree3
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate1SAA964003-2002
CCC Certificate2024010304654684
Declaration of Conformity - CE1SAD101100-3602
Declaration of Conformity - UKCA1SAD201100-3602
UL CertificateE48139-19990512
Package Level 1 Unitscarton 1 piece
Package Level 1 Width101 mm
Package Level 1 Depth / Length89 mm
Package Level 1 Height49.5 mm
Package Level 1 Gross Weight0.386 kg
Package Level 1 EAN4016779666619
Object Classification CodeF
ETIM 9EC001080 - Electronic overload relay
eClassV11.0 : 27371502
UNSPSC39122330
IDEA Granular Category Code (IGCC)5365 >> Electronic overload relay
Source URLhttps://new.abb.com/products/1SAX211001R1102/e45du-45
ABB Taxonomy PathLow Voltage Products and Systems > Control Products > Contactors > Electronic Overload Relays
ABB Classification IDs9AAC910006, 9AAC100110, 9AAC129021
Conventional Free-air Thermal Current (I<sub>th</sub>)Auxiliary Circuit NC 6 A
Rated Operational Current AC-15 (I<sub>e</sub>)(240 V) NC 3 A
Rated Operational Current DC-13 (I<sub>e</sub>)(125 V) NC 0.55 A
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Suitable ForA26
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 16-10 AWG
CQC CertificateCQC2006010309192161
Declaration of Conformity - CCC2020980309000293
ETIM 10EC001080 - Electronic overload relay
Replacement Part ID1SAX221001R1102
Mounting Position1 ... 6
Dimension Diagram1SAX200401F0001
Setting Range15 ... 45 A
Rated Operational Current (I<sub>e</sub>)45 A
Ambient Air Temperature CompensationYes
RMRS Certificate1SAA964000-0703
Number of Protected Poles3
Data Sheet, Technical Information (Part 2)1SAX100502F0002