GAE75-10-11 42V DC
رقم القطعة: 1SBL419025R8211
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
رقم القطعة: 1SBL419025R8211
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
كونتاكتور GAE75-10-11 42V DC
| Extended Product Type | GAE75-10-11 42V DC |
|---|---|
| Product ID | 1SBL419025R8211 |
| EAN | 3471522113825 |
| Catalog Description | GAE75-10-11 42V DC Contactor |
| Long Description | GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant of the power circuit to be controlled. GAE 75 contactors are of the block type design. - Main poles: the contactors are fitted with arc chutes with permanent magnets specially designed for DC breaking. The three contactor paths are arranged in series via two supplied and fitted insulated connections (25 mm²). The GAE75 are "single-pole" devices for which the connection polarities indicated next to the connection terminals must be respected. Furthermore, they are marked 1L1 for the positive terminal and 2T1 for the negative terminal. - Auxiliary contact: 1 CAL 5-11 side-mounted add-on auxiliary contact block (GAE75-10-11 types) - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available |
| Display Name | GAE75-10-11 42V DC |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Data Sheet, Technical Information | 1SBC100122C0202_Ch02 |
| Instructions and Manuals | FPTC407691P0003 |
| Product Net Width | 94 mm |
| Product Net Depth / Length | 108 mm |
| Product Net Height | 132 mm |
| Product Net Weight | 1.3 kg |
| Number of Main Contacts NO | 1 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | for 0.1 s 140 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-4-1 1000 V |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) | 8 kV |
| Maximum Electrical Switching Frequency | 300 cycles per hour |
| Mechanical Durability | 5 million |
| Rated Control Circuit Voltage (U<sub>c</sub>) | DC Operation 42 V |
| Coil Consumption | Average Holding Value, from Warm State 4 W |
| Power Loss | at Rated Operating Conditions per Pole 0.1 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Connecting Capacity Main Circuit | Flexible with Cable End 6 ... 16 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 1000 V DC |
| General Use Rating UL/CSA | (1000 V DC) 35 A |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| CB Certificate | CB_CN45325 |
| CCC Certificate | CCC_2018010304129268 |
| Declaration of Conformity - CE | 1SBD250807U1000 |
| Declaration of Conformity - UKCA | 1SBD250824U1000 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 140 mm |
| Package Level 1 Depth / Length | 146 mm |
| Package Level 1 Height | 96 mm |
| Package Level 1 Gross Weight | 1.3 kg |
| Package Level 1 EAN | 3471522113825 |
| Object Classification Code | Q |
| ETIM 7 | EC002552 - Power contactor, DC switching |
| ETIM 8 | EC002552 - Power contactor, DC switching |
| ETIM 9 | EC002552 - Power contactor, DC switching |
| eClass | V11.0 : 27371018 |
| UNSPSC | 39121529 |
| Source URL | https://new.abb.com/products/1SBL419025R8211/gae75-10-11-42v-dc |
| ABB Taxonomy Path | Low Voltage Products and Systems > Control Products > Contactors > DC Switching Contactors > GA Contactors |
| ABB Classification IDs | 9AAC910006, 9AAF637104, 9AAC184314, 9AAC202388 |
| Conventional Free-air Thermal Current (I<sub>th</sub>) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A |
| Rated Operational Current AC-15 (I<sub>e</sub>) | (500 V) 2 A |
| Rated Operational Current DC-13 (I<sub>e</sub>) | (24 V) 6 A / 144 W |
| Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A |
| Minimum Switching Capacity | 17 / 5 VLT4K |
| Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² |
| CQC Certificate | CQC2018010304129268 |
| Declaration of Conformity - CCC | 2020980304001625 |
| Rated Operational Current DC-5 (I<sub>e</sub>) | (110 V) 1-Pole, 40 °C 85 A |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Operate Time | Between Coil De-energization and NC Contact Closing 8 ... 18 ms |
| Mounting by Screws (not supplied) | 2 x M6 Screws Placed Diagonally |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Rated Operational Current DC-1 (I<sub>e</sub>) | (1000 V) 1-Pole, 40 °C 35 A |
| Rated Operational Current DC-3 (I<sub>e</sub>) | (110 V) 1-Pole, 40 °C 120 A |
| UL Listing Card | UL_E319322 |
| Connecting Terminals (delivered in open position) Main Poles | M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
| CSA Certificate | CSA_1033838_LR056745 |