OVR T1-T2 3N 12.5-275s P TS QS
رقم القطعة: 2CTB815710R0700
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
رقم القطعة: 2CTB815710R0700
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
جهاز حماية من الجهد العابر، فئة I OVR T1-T2 3N 12.5-275s P TS QS، رباعي الأقطاب
| Extended Product Type | OVR T1-T2 3N 12.5-275s P TS QS |
|---|---|
| Product ID | 2CTB815710R0700 |
| EAN | 3660308524928 |
| Catalog Description | OVR T1-T2 3N 12.5-275s P TS QS Surge Protective Device |
| Long Description | Surge protective devices SPD type 1- type 2 protect low-voltage consumer systems against lightning currents and surge voltages as they are tested as SPD type 1 and type 2 according to IEC 61643-11. The devices are compatible with the System pro M compact series. The SPD with "TS" are optionally equipped with a auxiliary contact. The variants with "reserve varistor" (s) offer additional protection for the system, as the SPD is not completely disconnected from the mains at the end of its service life, but with an additional smaller varistor still guarantees basic protection and the system thus until the surge arrester is replaced is still protected |
| Display Name | OVR T1-T2 3N 12.5-275s P TS QS |
| Data Sheet, Technical Information | 2CTC431039D0201 |
| Instructions and Manuals | 2CTC431030M1701 |
| Product Net Width | 71.2 mm |
| Product Net Depth / Length | 76.7 mm |
| Product Net Height | 95.8 mm |
| Product Net Weight | 0.6 kg |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 4P |
| Standards | IEC 61643-11 / EN 61643-11 |
| Power Loss | Total 63 mW |
| Degree of Protection | IP20 |
| Width in Number of Modular Spacings | 4 |
| Maximum Operating Altitude Permissible | Without Derating 5000 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| REACH Declaration | 9AKK107492A1906 |
| RoHS Declaration | 9AKK108466A4617 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| EcoSolutions Profile | 9AKK108472A3406 |
| Environmental Product Declaration - EPD | 9AKK108472A1709 |
| Declaration of Conformity - CE | 9AKK108466A4617 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.600 kg |
| Object Classification Code | 141BCC |
| ETIM 9 | EC001457 - Combined arrester for power supply systems |
| eClass | V11.0 : 27130808 |
| UNSPSC | 39121610 |
| E-Number (Finland) | 3217660 |
| E-Number (Norway) | 1623935 |
| Source URL | https://new.abb.com/products/2CTB815710R0700/ovr-t1-t2-3n-12-5-275s-p-ts-qs |
| ABB Taxonomy Path | Low Voltage Products and Systems > Modular DIN Rail Products > Surge Protective Devices SPDs > Surge Protective Devices SPD Class I |
| ABB Classification IDs | 9AAC910006, 9AAC100511, 9AAC183883 |
| SCIP | eb870ea9-6bc9-4c32-80f0-da19296d1169 Bulgaria |
| Short-Circuit Protective Devices | Curve B Breakers ≤ 125 A |
| Suitable For | To protect the systems against the transient overvoltage (lightning) |
| CQC Certificate | 9AKK107680A1975 |
| ETIM 10 | EC001457 - Combined arrester for power supply systems |
| Number of Protected Poles | 4 |
| Mechanical Drawings | 2CTC800015F1200.pdf |
| Fuse Size | 4 modular spacing |
| Mounting Type | DIN-Rail |
| Product Type | QS |
| Version | Plug-in |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| RoHS Date | 20230707 |
| REACH Date | 20231212 |
| Declaration | 2CTC432056G1701 |
| Carbon Footprint (Full Lifecycle) | 7.670846 kg CO₂ eq |
| Voltage Protection Level ( Up) | (L-N) 1.4 kV |
| Position of Neutral Terminals | Right |
| Options Provided | Industry, commercial building |
| Type of Low Voltage Distribution System | TT |
| Nominal AC Voltage of the System (U<sub>o</sub>) | 230 / 400 V |
| Maximum Continuous Operating Voltage (U<sub>c</sub>) | (L-PE) 275 V |
| Temporary Overvoltage Test Value (U<sub>T</sub>) | (L-N) 337 V |
| Discharge Current | Nominal 20 kA |
| Impulse Current | I (imp, 10 / 350 µs, L-N) 12.5 kA |
| Short Circuit Withstand Icc | 100 kA |
| Arrester Class | I |
| Auxiliary Circuit Load | Minimum 12Vdc - 10mA |
| Preventive Maintenance Feature | Yes |
| Status Indicator | Yes |
| Follow Current Extinction Capacity If (I fi) | (L-N) - kA |
| Lightning Impulse Current | 12.5 kA |