| Feature 1 | Rated data : Nominal voltage UN : 100 V, 230 V, 400 V, Nominal frequency fN : 50/60 Hz, Operating range: 0.05…2.0 x UN |
|---|---|
| Feature 2 | Power consumption : <1 VA at UN |
| Feature 3 | Thermal rating : continuously 2 x UN |
| Feature 4 | Dropout to pickup ratio : f>: > 99.99 % f<: < 100.02 % |
| Feature 5 | Dropout time : 30 ms |
| Feature 6 | Time lag error class index E : ± 10 ms |
| Feature 7 | Minimum operating time : 60 ms |
| Feature 8 | Max. allowed interruption of the auxiliary supply without influence to the function of the device : 50 ms |
| Source URL | https://cselectric.co.in/products-solutions/protectionandmeasurementdevices/generator-solutions/mrf2-frequency-relay/ |
| C&S Taxonomy Path | products-solutions > protectionandmeasurementdevices > generator-solutions > mrf2-frequency-relay |
| C&S Category | protectionandmeasurementdevices |
| Datasheet URL | https://cselectric.co.in/wp-content/uploads/2016/05/MRF-2.pdf |
| Download Brochure | Download Brochure <!-- |
| Feature 9 | Influences on frequency measuring : Aux. voltage : in the range 0.8 < UH / UHN < 1.2 no additional influences to be measured |
| Feature 10 | Frequency : no influences |
| Feature 11 | Influences on delay time : no additional influences to be measured |
| Summary | C&S Electric offers a frequency protection relay with df/dt: MRF2 with Nominal voltage UN: 100 V, 230 V, 400 V, nominal frequency fN: 50/60 Hz. Know more |
| C&S Subcategory | generator-solutions |
| Frequency Protection Relay with df/dt : MRF2 | RANGE Rated data : Nominal voltage UN : 100 V, 230 V, 400 V, Nominal frequency fN : 50/60 Hz, Operating range: 0.05…2.0 x UN Power consumption : <1 VA at UN Thermal rating : continuously 2 x UN Dropout to pickup ratio : f>: > 99.99 % f<: < 100.02 % Dropout time : 30 ms Time lag error class index E : ± 10 ms Minimum operating time : 60 ms Max. allowed interruption of the auxiliary supply without influence to the function of the device : 50 ms Influences on frequency measuring : Aux. voltage : in the range 0.8 < UH / UHN < 1.2 no additional influences to be measured Frequency : no influences Influences on delay time : no additional influences to be measured Contact Our Experts Download Brochure </ |