L02SCPU - Number of I/O points: 1024, number of I/O device points: 8192, program capacity: 20K…

رقم القطعة: L02SCPU_3

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

L02SCPU - Number of I/O points: 1024, number of I/O device points: 8192, program capacity: 20K…

المواصفات

Basic information / Model nameL02SCPU
Basic information / OverviewNumber of I/O points: 1024, number of I/O device points: 8192, program capacity: 20K steps, basic operation processing speed (LD X0): 60 ns, program memory capacity: 80K bytes, external interface: USB/RS-232, built-in I/O: sink output
Basic information / Sales statusDiscontinued
Listed / Model nameL02SCPU 2024/09 Discontinued
WeightCPU: 0.32 kg END cover (accessory): 0.06 kg
Basic information / Conformance standardUL cUL CE(EMC) CE(RoHS) KC(EMC)
Basic information / End of order date2024/09
Basic information / Discontinued date2024/09*Please check or inquire it in each overseas sales company site because the sale situation is different depending on each countries.
Basic information / Replacement modelsL06CPU Learn more about our products Compare replacement models and specifications
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147 m/s2, 3 times each in 3 directions X, Y, Z)
Operating atmosphereNo corrosive gases
Operating altitude0...2000 m
Installation locationInside a control panel
Overvoltage categoryII or less
Pollution degree2 or less
Basic information / Repair support expiration date2031/09
Operating ambient temperature0...55 ˚C
Storage ambient temperature-25...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
I/O control modeRefresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).)
Number of I/O points1024 points (X/Y0...3FF)
Control methodStored program cyclic operation
Listed / OutlineNumber of I/O points: 1024, number of I/O device points: 8192, program capacity: 20K steps, basic operation processing speed (LD X0): 60 ns, program memory capacity: 80K bytes, external interface: USB/RS-232, built-in I/O: sink output
Allowable momentary power failure timeThe time differs depending on the power supply module used.
Constant scan0.5...2000 ms (setting is available in increments of 0.5 ms by parameter)
Programming language / Sequence control languageRelay symbol language, logic symbolic language, MELSAP3 (SFC), MELSAP-L, function block and structured text (ST)
Processing speed / Sequence instruction / LD X060 ns
Processing speed / Sequence instruction / MOV D0 D1120 ns
Program capacity20K steps (80K bytes)
Memory capacity / Program memory (drive 0)80K bytes
Memory capacity / Standard RAM (drive 3)128K bytes
Memory capacity / Standard ROM (drive 4)512K bytes
Maximum number of storable files / Program memory64
Maximum number of storable files / Standard RAM4
Maximum number of storable files / Standard ROM128
Maximum number of intelligent function module parameters / Initial setting2048 parameters
Maximum number of intelligent function module parameters / Refresh1024 parameters
Number of I/O device points8192 points (X/Y0...1FFF)
No. of device points / Internal relay (M)8192 points (M0...8191) by default (changeable)
No. of device points / Latch relay (L)8192 points (L0...8191) by default (changeable)
No. of device points / Link relay (B)8192 points (B0...1FFF) by default (changeable)
No. of device points / Timer (T)2048 points (T0...2047) by default (changeable) (Low-speed and high-speed timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
No. of device points / Retentive timer (ST)0 points by default (changeable) (Low-speed and high-speed retentive timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed retentive timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed retentive timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
No. of device points / Counter (C)Normal counter: 1024 points (C0...1023) by default (changeable)
No. of device points / Data register (D)12288 points (D0...12287) by default (changeable)
No. of device points / Extended data register (D)32768 points (D12288...45055) by default (changeable)
No. of device points / Link register (W)8192 points (W0...1FFF) by default (changeable)
No. of device points / Extended link register (W)0 points by default (changeable)
No. of device points / Annunciator (F)2048 points (F0...2047) by default (changeable)
No. of device points / Edge relay (V)2048 points (V0...2047) by default (changeable)
No. of device points / File register (R) / Standard RAM32768 points (R0...32767) (Maximum 65536 points are available by switching blocks.)
No. of device points / File register (ZR) / Standard RAM65536 points (ZR0...65535) (Blocks do not need to be switched.)
No. of device points / Link special relay (SB)2048 points (SB0...7FF) by default (changeable)
No. of device points / Link special register (SW)2048 points (SW0...7FF) by default (changeable)
No. of device points / Step relay (S)8192 points (S0...8191) by default
No. of device points / Index register/standard device register (Z)20 points (Z0...19) (maximum)
No. of device points / Index register (Z) (32-bit index modification of ZR device)10 points (Z0...18) (maximum) (The index register is used as a double-word device.)
No. of device points / Pointer (P)4096 points (P0...4095) (The number of device points is fixed.) (The local pointer range and the common pointer range can be set by parameter.)
No. of device points / Interrupt pointer (I)256 points (I0...255) (The number of device points is fixed.) (The fixed scan interval for the system interrupt pointer I28 to 31 can be set by parameter.) 0.5...1000.0 ms (in increments of 0.5 ms) Default I28: 100 ms, I29: 40 ms, I30: 20 ms, I31: 10 ms
No. of device points / Special relay (SM)2048 points (SM0...2047) (The number of device points is fixed.)
No. of device points / Special register (SD)2048 points (SD0...2047) (The number of device points is fixed.)
No. of device points / Function input (FX)16 points (FX0...F) (The number of device points is fixed.)
No. of device points / Function output (FY)16 points (FY0...F) (The number of device points is fixed.)
No. of device points / Function register (FD)5 points (FD0...4) (The number of device points is fixed.)
Link direct deviceDevice that directly accesses the link device of a network module Specification format: J□□\X□□, J□□\Y□□, J□□\SB□□, J□□\W□□, J□□\SW□□
Intelligent function module deviceDevice that directly accesses the buffer memory of an intelligent function module Specified form: U...\G...
Latch (data retention during power failure) range8192 points (L0...8191) by default (The latch range can be set for the devices, B, F, V, T, ST, C, D, W, and R.)
Clock function / Displayed informationYear, month, date, hour, minute, second, and day of week (automatic leap year detection)
Clock function / Accuracy0 ˚C: -2.96...+3.74 s (TYP. +1.42 s)/day 25 ˚C: -3.18...+3.74 s (TYP. +1.50 s)/day 55 ˚C: -13.20...+2.12 s (TYP. -3.54 s)/day
Internal current consumption (5 V DC)Without display unit: 0.75 A END cover (accessory): 0.04 A
External dimensions / Height90 mm
External dimensions / WidthCPU: 70 mm END cover (accessory): 13 mm
External dimensions / Depth95 mm
High-speed input / 24V Input / Rated input voltage24 V DC (+20/-15 %, ripple ratio within 5 %)
High-speed input / 24V Input / Rated input current6.0 mA TYP. (at 24 V DC)
High-speed input / 24V Input / On voltage/on current19 V or more/5 mA or more
High-speed input / 24V Input / Off voltage/off current8 V or less/1.5 mA or less
High-speed input / 24V Input / Input resistance3.8 kΩ
High-speed input / 24V Input / Response time10 µs or less
High-speed input / 24V Input / Common terminal arrangementIndependent common
High-speed input / Differential inputEIA Standard RS-422-A Differential line driver level (AM26L31 (Manufactured by Texas Instruments Incorporated) or equivalent)
Standard input / 24V Input / Rated input voltage24 V DC (+20/-15 %, ripple ratio within 5 %)
Standard input / 24V Input / Rated input current4.1 mA TYP. (at 24 V DC)
Standard input / 24V Input / ON voltage/ON current19 V or more/3.5 mA or more
Standard input / 24V Input / OFF voltage/OFF current8 V or less/1.0 mA or less
Standard input / 24V Input / Input resistance5.6 kΩ
Standard input / 24V Input / Response time100 µs or less
Standard input / 24V Input / Common terminal arrangement10 points/common
Output / Rated load voltage5...24 V DC
Output / Maximum load current0.1 A/point
Output / Maximum voltage drop at ON0.2 V (TYP.)
Output / Leakage current at OFF0.1 mA or less
Output / Response time1 µs or less
Output / Common terminal arrangement8 points/common (sink type)
Vibration resistance / Compliant with .. d IEC 61131-2 / Under intermittent vibration ~62dc24Frequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s2 Sweep count: 10 times each in X, Y, Z directions
Vibration resistance / Compliant with .. and IEC 61131-2 / Under continuous vibration ~d68864Frequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s2
Equipment classClass I
Listed / Large categoriesProgrammable controller CPU