Mitsubishi Electric

Q00UJCPU - Number of I/O points: 256, number of I/O device points: 8192, program size: 10K steps,…

رقم القطعة: Q00UJCPU_3827

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

Q00UJCPU - Number of I/O points: 256, number of I/O device points: 8192, program size: 10K steps,…

المواصفات

Basic information / Model nameQ00UJCPU
Basic information / OverviewNumber of I/O points: 256, number of I/O device points: 8192, program size: 10K steps, processing speed (LD X0): 120 ns, program size: 40K bytes, peripheral connection ports: USB/RS-232, without memory card interface, base: 5 slots, power supply: 100...240 V AC input/5 V DC 3A output
Basic information / Sales statusOn sale
Listed / Model nameQ00UJCPU
Weight0.70 kg
Basic information / Conformance standardUL cUL CE(EMC) CE(LVD) CE(RoHS) KC(EMC) LR NK DNV ABS RINA BV
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147 m/s2, 3 times each in 3 directions X, Y, Z)
Operating atmosphereNo corrosive gases
Operating altitude0...2000 m
Installation locationInside a control panel
Overvoltage categoryII or less
Pollution degree2 or less
Inrush current40 A, within 8 ms
Withstand voltageBetween the input and LG batched terminal and the output and FG batched terminal, 2300 V AC per minute (altitude 0...2000 m)
Insulation resistanceInput and LG batched, output and FG batched, batch input-LG, batch output-FG: 10 MΩ or higher by 500 VDC insulation resistance tester
Operating ambient temperature0...55 ˚C
Storage ambient temperature-25...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
I/O control modeRefresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).)
Number of I/O points256 points (X/Y0...FF)
Control methodStored program cyclic operation
Listed / OutlineNumber of I/O points: 256, number of I/O device points: 8192, program size: 10K steps, processing speed (LD X0): 120 ns, program size: 40K bytes, peripheral connection ports: USB/RS-232, without memory card interface, base: 5 slots, power supply: 100...240 V AC input/5 V DC 3A output
Allowable momentary power failure timeWithin 20 ms (100 V AC or more)
Clock functionYear, month, date, hour, minute, second, and day of week (automatic leap year detection) Accuracy: -2.96...+3.74 s (TYP. +1.24 s)/d at 0 ˚C Accuracy: -2.34...+3.74 s (TYP. +1.63 s)/d at 25 ˚C Accuracy: -11.48...+2.12 s (TYP. -3.03 s)/d at 55 ˚C
Constant scan0.5...2000 ms (setting is available in increments of 0.5 ms by parameter)
Programming language / Sequence control languageRelay symbol language, logic symbolic language, MELSAP3 (SFC), MELSAP-L, function block and structured text (ST)
Processing speed / Sequence instruction / LD X0120 ns
Processing speed / Sequence instruction / MOV D0 D1240 ns
Program capacity10K steps (40K bytes)
Memory capacity / Program memory (drive 0)40K bytes
Memory capacity / Standard ROM (drive 4)256K bytes
Maximum number of storable files / Program memory32
Maximum number of storable files / Standard ROM128
Maximum number of intelligent function module parameters / Initial setting512 parameters
Maximum number of intelligent function module parameters / Refresh256 parameters
Number of I/O device points8192 points (X/Y0...1FFF)
No. of device points / Internal relay (M)8192 points (M0...8191) by default (changeable)
No. of device points / Latch relay (L)8192 points (L0...8191) by default (changeable)
No. of device points / Link relay (B)8192 points (B0...1FFF) by default (changeable)
No. of device points / Timer (T)2048 points (T0...2047) by default (changeable) (Low-speed and high-speed timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
No. of device points / Retentive timer (ST)0 points by default (changeable) (Low-speed and high-speed retentive timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed retentive timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed retentive timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
No. of device points / Counter (C)Normal counter: 1024 points (C0...1023) by default (changeable)
No. of device points / Data register (D)12288 points (D0...12287) by default (changeable)
No. of device points / Link register (W)8192 points (W0...1FFF) by default (changeable)
No. of device points / Annunciator (F)2048 points (F0...2047) by default (changeable)
No. of device points / Edge relay (V)2048 points (V0...2047) by default (changeable)
No. of device points / Link special relay (SB)2048 points (SB0...7FF) by default (changeable)
No. of device points / Link special register (SW)2048 points (SW0...7FF) by default (changeable)
No. of device points / Step relay (S)8192 points (S0...8191) by default (changeable)
No. of device points / Index register/standard device register (Z)20 points (Z0...19) (maximum)
No. of device points / Pointer (P)512 points (P0...511) (The number of device points is fixed.) (The local pointer range and the common pointer range can be set by parameter.)
No. of device points / Interrupt pointer (I)128 points (I0...127) (The number of device points is fixed.) (The fixed scan interval for the system interrupt pointer I28 to 31 can be set by parameter.) 0.5...1000.0 ms (in increments of 0.5 ms) Default I28: 100 ms, I29: 40 ms, I30: 20 ms, I31: 10 ms
No. of device points / Special relay (SM)2048 points (SM0...2047) (The number of device points is fixed.)
No. of device points / Special register (SD)2048 points (SD0...2047) (The number of device points is fixed.)
No. of device points / Function input (FX)16 points (FX0...F) (The number of device points is fixed.)
No. of device points / Function output (FY)16 points (FY0...F) (The number of device points is fixed.)
No. of device points / Function register (FD)5 points (FD0...4) (The number of device points is fixed.)
Link direct deviceDevice that directly accesses the link device of a network module Specification format: J□□\X□□, J□□\Y□□, J□□\SB□□, J□□\W□□, J□□\SW□□
Intelligent function module deviceDevice that directly accesses the buffer memory of an intelligent function module Specified form: U...\G...
Latch (data retention during power failure) range8192 points (L0...8191) by default (The latch range can be set for the devices, B, F, V, T, ST, C, D, and W.)
Internal current consumption (5 V DC)0.37 A
External dimensions / Height98 mm
External dimensions / Width245 mm
External dimensions / Depth98 mm
Vibration resistance / Compliant with .. d IEC 61131-2 / Under intermittent vibration ~62dc24Frequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s2 Sweep count: 10 times each in X, Y, Z directions
Vibration resistance / Compliant with .. and IEC 61131-2 / Under continuous vibration ~d68864Frequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s2
Equipment classClass I
Listed / Large categoriesProgrammable controller CPU
Listed / Medium categoriesUniversal model
External interfaceTerminal block (M3.5 screw)
RUN/PAUSE contactOne contact can be set up in X0 to X1FFF for each of RUN and PAUSE.
Input power supply voltage100...240 V AC (-15 %...+10 %)
Input frequency50/60 Hz ±5 %
Input voltage distortionWithin 5 %
Maximum input apparent power105 VA
Rated output current / 5 V DC3 A
Overcurrent protection / 5 V DC3.3 A or more
Overvoltage protection / 5 V DC5.5...6.5 V
Efficiency65 % or more
Operation indicationLED indication (The POWER LED of the CPU part: Normal: On (green), Error: Off)
FuseBuilt-in (user-unchangeable)
Contact output sectionNone
Number of mountable I/O modules5
Applicable moduleMELSEC-Q series modules