The XP95 Input/Output Module – Three Channel – Isolating is used to control and monitor the operation of a circuit of conventional sounders or bells. EN 54-17 & EN 54-18 Certified Allows independent monitoring of input channels Allows independent control of output relays XP95, Discovery compatible
| General / Warranty | 10 year |
|---|---|
| Conformance / Approvals | CPR, VdS, LPCB |
| Mechanical / Colour | White |
| Environmental / Operating temperature (max) | 70°C |
| Environmental / Operating temperature (min) | -20°C |
| Environmental / Operating temperature | -20 to 70°C |
| Environmental / IP rating Value | IP54 |
| Electrical / Supply voltage (min) | 17V dc |
| Environmental / Operating temperature (imperial) | -4 to 158°F |
| Electrical / Supply voltage (max) | 28V dc |
| Environmental / Operating temperature (max) (imperial) | 158°F |
| Electrical / Supply voltage (Vmin-Vmax) | 17 to 28V dc |
| Environmental / Operating temperature (min) (imperial) | -4°F |
| Environmental / Humidity (max) | 95%, RH |
| Environmental / Humidity (min) | 0%, RH |
| Environmental / Humidity Note | no condensation or icing |
| Electrical / Protocol voltage | 5 to 9V peak to peak |
| Environmental / Humidity | 0% to 95% (no condensation or icing) |
| Electrical / Protocol voltage (max) | 9V |
| Electrical / Protocol voltage (min) | 5V |
| Electrical / Power-up surge current | 6.5mA |
| Electrical / Maximum power-up time | 150ms |
| Mechanical / Relay output contact rating | 1A |
| Mechanical / Relay output rating tested at | 30V ac |
| Electrical / On resistance | 0.2Ω |
| Electrical / Quiescent current, 20kΩ EOL fitted | 3mA |
| Electrical / Maximum continuous current | 1A |
| Electrical / Maximum switching current | 3A |
| Electrical / Switch input monitoring voltage | 9 to 11V dc |
| Electrical / Switch input monitoring voltage (max) | 11V dc |
| Electrical / Switch input monitoring voltage (min) | 9V dc |
| Electrical / Maximum cable resistance | 50Ω |
| Apollo Part Number | 55000-588APO |
| Apollo Range | xp95 |
| Apollo Category | interface-face-plate |
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر
Apollo Fire Detectors
اطلب عرض سعر