Apollo | K1810-13 Extinguishing Panel
رقم القطعة: K1810-13
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
رقم القطعة: K1810-13
لا يعرض أي بائع سعرًا لهذا المنتج بعد.
للطلب والدفع استخدم تطبيق ENG.
The Apollo K1810-13 Extinguishing Panel provides reliable and accurate control for fire suppression systems. It delivers fast response, clear system monitoring, and stable performance in critical environments. This panel supports clean agent and gaseous fire extinguishing systems such as FM-200, CO₂, and NOVEC 1230. The panel continuously monitors detection circuits, release outputs, and manual controls. It gives instant visual and audible indications to help operators identify system status quickly. As a result, response time improves and system safety increases. The Apollo K1810-13 Extinguishing Panel includes manual release and abort functions to ensure full control during emergency situations. These features help operators activate or stop the extinguishing process safely and efficiently. In addition, the intuitive interface simplifies daily operation and routine maintenance. Moreover, the compact metal enclosure allows easy wall mounting and fast installation. The panel fits perfectly in control rooms, electrical rooms, and protected areas. It also supports stable operation in demanding industrial and commercial environments. This panel suits a wide range of applications. Typical installations include data centers, server rooms, archives, telecom rooms, and industrial facilities. Therefore, the Apollo K1810-13 Extinguishing Panel offers a dependable solution for modern fire suppression systems.
| Specifications / Powersupplyrating | 3Ampstotalincludingbatterycharge28V+/-2V |
|---|---|
| Specifications / Maximumripplecurrent | 200millivolts |
| Specifications / Batterychargevoltage | 27.6VDCnominal(temperaturecompensated) |
| Specifications / Batterychargecurrent | 0.7Amaximum |
| Specifications / Batteryfuse | 20mm,3.15Aglass |
| Specifications / Maximumcurrentdrawfrombatteries | 3amps |
| Specifications / Quiescentcurrentofpanelinmainsfail | 0.095A |
| Specifications / Sounderoutputs | 24VFusedat500mAwithelectronicfuse |
| Specifications / Faultrelaycontactrating | 30VDC1AAmpmaximum |
| Specifications / Firerelaycontactrating | 30VDC1AAmpmaximum |
| Specifications / Localfirerelaycontactrating | 30VDC1AAmpmaximum |
| Specifications / Firststagecontactrating | 30VDC1AAmpmaximum |
| Specifications / Secondstagecontactrating | 30VDC1AAmpmaximum |
| Specifications / Extractcontactrating | 30VDC1AAmpmaximum |
| Specifications / Zonequiescentcurrent | 2mAmaximum |
| Specifications / Terminalcapacity | 12AWG |
| Specifications / NACrating | 0.5Apercircuit |
| Specifications / Monitoredinputendofline | 6K85%1/2Wattresistor |
| Specifications / ExtinguishantoutputEOL | 1N4004Diode |
| Specifications / Detectoralarmthreshold | 999 ohms to 400 ohms |
| Specifications / Call point alarm threshold | 399 ohms to 100 ohms |
| Specifications / Monitored inputs normal threshold | 8K ohms to 1k ohm |
| Specifications / Monitored inouts alarm threshold | 999 ohms to 100 ohms |
| Specifications / Monitored inputs short circuit threshold | 99 ohms to 0 ohms |
| Specifications / Inputs | 1stStage |