The TR-2100 is an intelligent analog/ addressable Fire Alarm Control Panels (FACP), which contains one built in signaling line circuit (SLC), which can support 159 sensors and 159 modules per loop. Additional SLC loops can be added using the model TR-6815 SLC expander to increase the overall point capacity to 2100 points per panel. TR-2100R, TR-2100B, TR-R2100R & TR-R2100B has the interconnection capability for up to 32 panels. The system has two modes of operation, multiple panels covering one larger building, or multiple independent buildings. The TR-R2100 can be used in a networked system where at least one TR-2100 is in the system without a display on the panel facia. The TR-R2100 is best with the same features of TR-2100. All these panels are feature-rich with detector sensitivity, day/night thresholds, drift compensation, pre-trouble maintenance alert, and calibration trouble alert and has eight on-board Flexput™ circuits that can be configured for auxiliary power, notification outputs, or for conventional smoke detector inputs (Class A or Class B). The FACP also has a Built in dual phone line digital alarm communicator / transmitter (DACT), IP or optional cellular technologies, Form C trouble relay, and two programmable Form C relays.
| Environmental / Operating Temperature | 32°F to 120°F (0°C to 49°C) |
|---|---|
| Environmental / Humidity | 0 to 93% relative humidity (noncondensing) |
| Environmental / Total Accessory Load | 9A @ 24VDC power-limited |
| Environmental / Standby Current | 230mA |
| Environmental / Alarm Current | 415mA |
| Environmental / Battery Charging Capacity | 17 to 55AH |
| Environmental / Battery Size | 18AH max. allowed in control panel |
| Environmental / TR-2100R AC | 240VAC @ 50/60Hz, 2.8A |
| Environmental / Notification Circuits | 3A per circuit @ 24VDC, |
| Environmental / Auxiliary Power Circuits | 3A per circuit @ 24VDC, |
| Environmental / Initiation Circuit | 100mA per circuit @ 24VDC, |