GEWISS

RESTART WITH AUTOTEST PRO - COUPLED WITH RCCB'S - 2 POLES - 40 A TYPE A[IR] Idn=0,3 A 230 V ac - 5 M

رقم القطعة: GW90918

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

RESTART WITH AUTOTEST PRO - COUPLED WITH RCCB'S - 2 POLES - 40 A TYPE A[IR] Idn=0,3 A 230 V ac - 5 MODULES EN 50022

المواصفات

Electrical characteristics-
StandardIEC EN 63024, IEC EN 61008-1, IEC EN 61008-2-1
Ware Number85362010
Source URLhttps://www.gewiss.com/ww/en/products/product.1000001.1000060.GW90918
GEWISS FamilyEnergy
GEWISS SeriesReStart Range-Automatic reclosing devices
GEWISS Taxonomy PathEnergy > ReStart Range-Automatic reclosing devices
Datasheet URLhttps://www.gewiss.com/content/gewiss/ww/en/products/product.datasheet.1000001.1000060.GW90918.pdf
Operating temperature-25°C ÷ +60°C
DescriptionAutomatic reclosing device
No. modules5
Stocking temperature-40°C ÷ +70°C
Use categoryAC12
Insulation voltage (Ui)500 V
Rated current40 A
Rated impulse withstand voltage (Uimp)4 kV
Rated voltage AC230 V
CodeReStart Autotest PRO 2P
Rated frequency (Hz)50 Hz
Mechanical endurance4000
Distribution systemTT - TN-S
Overvoltage categoryIII
Dielectric strength test voltage between pole and earth2500 a.c. for 1 minute
Type of residual current protectionA [IR]
Rated residual operating current300 mA
Rated non-operating resistance between live parts and earth (Rdo)2.5 kΩ
Type of contactsPhotomos (potential free)
Voltage operating5÷230 a.c. / d.c.
Rated operating resistance between live parts and earth (Rd)5 kΩ
Current operating0.6 (min) - 100 cosφ=1 (max)
Maximum operating frequency30 oper./h
Operating frequency50 Hz
Operating modesNO/NC/NC + pulse
Terminal section≤ 2.5 mm²
Automatic reclosure for untimely trippingYes
Earth failure testYes
Continuous system monitoringYes
Autotest (automatic RCCB protection test)Yes
Completeable withGW90992 RS485 BUS Module
Number of poles2P
MECHANICAL CHARACTERISTICS-
FEATURE AUXILIARY CONTACT-
AUTOTEST FUNCIONT-
RESTART FUNCTIONFUN-