Mitsubishi Electric

QS0J65BTS2-8D - DC input: 8 points (double input), 16 points (single input), 24 V DC, 5.9 mA,…

رقم القطعة: QS0J65BTS2-8D_3461

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

QS0J65BTS2-8D - DC input: 8 points (double input), 16 points (single input), 24 V DC, 5.9 mA,…

المواصفات

Basic information / Model nameQS0J65BTS2-8D
Basic information / OverviewDC input: 8 points (double input), 16 points (single input), 24 V DC, 5.9 mA, response time: 0.4 ms, 16 points/common, negative common type, spring-clamp terminal block
Basic information / Sales statusDiscontinued
Listed / Model nameQS0J65BTS2-8D 2023/09 Discontinued
Weight0.46 kg
Basic information / Conformance standardUL cUL CE(EMC) CE(Machinery) CE(RoHS) IEC 61508 IEC 62061 EN ISO 13849-1 KC(EMC)
Basic information / End of order date2023/06
Basic information / Discontinued date2023/09*Please check or inquire it in each overseas sales company site because the sale situation is different depending on each countries.
Basic information / Replacement modelsNZ2GNSS2-8D Learn more about our products Compare replacement models and specifications
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147 m/s2, duration of action 11 ms, 3 times in X, Y, Z directions respectively by sine half-wave pulse)
Operating atmosphereNo corrosive gases
Operating altitude0...2000 m
Installation locationInside a control panel
Overvoltage categoryII or less
Pollution degree2 or less
Insulation resistanceBetween all DC external terminals and ground: 10 MΩ or higher by 500 V DC insulation resistance tester
Basic information / Repair support expiration date2030/09
Operating ambient temperature0...55 ˚C
Storage ambient temperature-40...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
Listed / OutlineDC input: 8 points (double input), 16 points (single input), 24 V DC, 5.9 mA, response time: 0.4 ms, 16 points/common, negative common type, spring-clamp terminal block
Input typeDC input (negative common type)
Dielectric withstand voltageBetween all DC external terminals and ground: 500 V AC for 1 minute
Vibration resistance / Compliant with .. d IEC 61131-2 / Under intermittent vibration ~62dc24Frequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s2 Sweep count: 10 times each in X, Y, Z directions
Vibration resistance / Compliant with .. and IEC 61131-2 / Under continuous vibration ~d68864Frequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s2
Equipment classClass III
Listed / Large categoriesSafety network
Listed / Medium categoriesCC-Link Safety
External interfaceCommunication part, module power supply part: 7-point two-piece terminal block (M3 screw) I/O power supply part, I/O part: two-piece spring clamp terminal block
Number of input points8 points (doubling input) 16 points (single input)
Rated input voltage24 V DC (ripple ratio: within 5 %) (allowable voltage range: 19.2...28.8 V DC)
Rated input currentApprox. 5.9 mA
Maximum number of simultaneous input points100 %
Station typeSafety remote I/O station
ON voltage/ON current15 V DC or more/2 mA or more
OFF voltage/OFF current5 V DC or less/0.5 mA or less
Input resistanceApprox. 4.3 kΩ
Input response time / OFF to ON0.4 ms or less (24 V DC)
Input response time / ON to OFF0.4 ms or less (24 V DC)
Input common terminal arrangement16 points/common (2-wire, spring clamp terminal block type)
Protection degreeIP2X
Module power supply / Voltage19.2...28.8 V DC (ripple ratio: within 5 %)
Module power supply / Current120 mA or less (at 24 V DC, all points ON)
Listed / Small categoriesSafety input
Safety remote station refresh response processing time9.6 ms
Input response time of safety remote station11.2 ms or less + time of noise removal filter (1 ms, 5 ms, 10 ms, 20 ms, 50 ms)
Module power supply / Protection functionModule power supply overvoltage protection function, module power supply overcurrent protection function
Module power supply / Fuse0.8 A (not replaceable)
Input isolation methodPhotocoupler
Number of occupied stations1 station
Number of accesses to nonvolatile memory inside module1012 times
External power supply / Voltage19.2...28.8 V DC (ripple ratio within 5 %)
External power supply / Current40 mA (at 24 V DC and all points ON, excluding the external load current)
External power supply / Protection functionExternal power supply overvoltage protection function, external power supply overcurrent protection function
External power supply / Fuse8 A (not replaceable)
Module power supply / Allowable momentary power failure timeWithin 10 ms