Eaton

Eaton Distribution parts

رقم القطعة: 279200

لا يعرض أي بائع سعرًا لهذا المنتج بعد.

للطلب والدفع استخدم تطبيق ENG.

الوصف

Eaton Distribution parts

المواصفات

Ambient operating temperature - max60 °C
Ambient operating temperature - min-25 °C
RAL-number7035
Special featuresMaximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
Product NameEaton Distribution parts
Catalog Number279200
Model CodeFI-40/4/003
EAN4015082792008
Product Length/Depth76 mm
Product Height80 mm
Product Width70 mm
Product Weight0.318 kg
CertificationsIEC/EN 61008
Source URLhttps://www.eaton.com/gb/en-gb/skuPage.279200.html
FeaturesAdditional equipment possible Residual current circuit breaker
TypeFIResidual current circuit breakersType AC
Degree of protectionIP20
Built-in depth69.5 mm
ColorGray
Width in number of modular spacings4
Mounting methodTop-hat rail IEC/EN 60715 DIN rail
Fitted with:Interlocking device
Number of polesFour-pole
Amperage Rating40 A
Rated operational voltage (Ue) - max400 V
Voltage rating230 V AC / 400 V AC
Rated operational current for specified heat dissipation (In)40 A
Frequency rating50 Hz
Pollution degree2
Rated insulation voltage (Ui)440 V
Frame45 mm
Rated impulse withstand voltage (Uimp)4 kV
Voltage typeAC
Connectable conductor cross section (multi-wired) - max16 mm²
Connectable conductor cross section (multi-wired) - min1.5 mm²
Connectable conductor cross section (solid-core) - max35 mm²
Connectable conductor cross section (solid-core) - min1.5 mm²
Heat dissipation per pole, current-dependent0 W
Equipment heat dissipation, current-dependent9.6 W
Static heat dissipation, non-current-dependent0 W
Heat dissipation capacity0 W
Terminal protectionProtection against electric shock to IEC 536
Enclosure width80 mm
Surge current capacity0.25 kA
Fault current rating30 mA
Impulse withstand currentPartly surge-proof 250 A
Leakage current typeAC
Sensitivity typeAC current sensitive
Rated short-time withstand current (Icw)10 kA
Busbar material thickness0.8 mm - 2 mm
Terminals (top and bottom)Twin-purpose terminals
Rated fault current - max0.03 A
Rated fault current - min0.03 A
Tripping timeNon-delayed
Rated short-circuit strength10 kA